Safety Alerts

Notice No. 1 7
July 23, 2003
ELECTRICAL WIRING
INSPECTION AND MAINTENANCE
Recently, there were two fires on
Pacific OCS Region platforms, both involving electrical wiring.
The first fire involved
deteriorated insulation on electrical wiring. Platform personnel had
started a generator located in an electrical room, to provide power
for a workover rig. Personnel smelled smoke, shut down the generator,
and notified other personnel. The workers inspected the electrical
room area but could not find the source of the odor. About half an
hour later, the generator was restarted. Within a few minutes, flames
were seen coming from under a control panel door. The generator was
then turned off and the flames extinguished themselves.
The cause of the accident was
determined to be an electrical short in the wiring in a control panel
supplying power from a generator to the workover rig and other
equipment. The insulation was cracked. The deteriorated wiring has
since been replaced. Other than the wiring, there was no damage and
there were no injuries as a result of the fire.
The second fire was the result of a
wiring failure in a generator. During a planned electrical shutdown,
the platform was operating under diesel generator power when the
generator stopped running. After the generator was restarted,
personnel entered the generator room a few minutes later and noticed
flames coming from the electrical generation portion of the generator.
The generator was then shut down, and the fire was extinguished with a
Halon fire extinguisher.
Analysis of the incident indicated
that the fire was caused by a short in the main rotor. The rotor had
been randomly wound with round wire which failed over time, causing
the unit to overheat and the grease at the bearings to catch fire.
After the fire, the operator had the generator repaired by replacing
and rewinding all the damaged components in accordance with factory
specifications. There were no injuries involved.
Most of the platforms in the
Pacific OCS Region are decades old; even the newest platforms were
installed in the 1980’s. Some of the equipment and wiring on the
platforms are quite old and require heightened vigilance to preclude
accidents and fires. Minerals Management Service regulations at 30 CFR
250.114 in part require proper classification of areas and proper
installation of electrical systems in accordance with American
Petroleum Institute Recommended Practices, but follow-up maintenance
is not specifically addressed.
In the interest of safety, we
recommend that operators consider using the following inspection
procedures to help prevent problems due to deteriorated wiring, with
necessary maintenance performed in case any problems are detected:
1. Periodic visual inspections of
electrical wiring, which at times may include wiring that is not
readily accessible without opening up equipment.
2. Periodic megging, a testing
procedure applying voltage across the stator windings of motors and
generators to verify that there are no shorts or deterioration in the
insulation. A megohmeter is used to calculate resistance by measuring
amperage and voltage drop due to resistance in stator windings. A
decrease in the insulation’s resistance can be an indicator of hot
spots, winding failure, or deterioration of the cable insulation.
3. Use of heat-sensing imaging to
help detect hotspots in electrical equipment and wiring.
This Safety Alert can be found on our Website
at: http://www.mms.gov
Web Master:
Nollie
Gildow-Owens
Page content last updated 09/20/2006
Page last published 09/20/2006 |